The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a cross to receive
the measured value.
The implementation for IEC61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA
then the DATAVALID output will be LOW.
18.14 GOOSE function block to receive a single point value
GOOSESPRCV
18.14.1 Identification
GUID-F2B30A70-842E-435E-8FAB-B1E58B9C0164 v1
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
single point value
GOOSESPRCV - -
18.14.2 Functionality
GUID-0C99A106-C131-45D3-9B81-6B188E35EB34 v2
GOOSESPRCV is used to receive a single point value using IEC61850 protocol via GOOSE.
18.14.3 Function block
GUID-A414F31A-323F-4684-BADA-46F9C5E2B0E8 v1
GOOSESPRCV
BLOCK ^SPOUT
DATAVALID
COMMVALID
TEST
IEC10000248-1-en.vsd
IEC10000248 V1 EN-US
Figure 613: GOOSESPRCV function block
18.14.4 Signals
PID-2527-INPUTSIGNALS v18
Table 919: GOOSESPRCV Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of function
1MRK 502 066-UUS B Section 18
Station communication
1203
Technical manual