PID-2527-OUTPUTSIGNALS v18
Table 920: GOOSESPRCV Output signals
Name Type Description
SPOUT BOOLEAN Single point output
DATAVALID BOOLEAN Data valid for single point output
COMMVALID BOOLEAN Communication valid for single point output
TEST BOOLEAN Test output
18.14.5 Settings
PID-2527-SETTINGS v18
Table 921: GOOSESPRCV Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
18.14.6 Operation principle
GUID-0E25A3FB-41BD-4EFE-9CA0-1262B9CD14CD v2
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure condition
and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a cross to receive
the binary single point values.
The implementation for IEC61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA
then the DATAVALID output will be LOW.
Section 18 1MRK 502 066-UUS B
Station communication
1204
Technical manual