18.15 GOOSE VCTR configuration for send and receive
GOOSEVCTRCONF
18.15.1 Identification
18.15.2 Settings
18.16 GOOSE voltage control receiving block GOOSEVCTRRCV
18.16.1 Identification
18.16.2 Signals
18.17 MULTICMDRCV and MULTICMDSND
SEMOD119881-1 v3
GUID-1A6E066C-6399-4D37-8CA5-3074537E48B2 v2
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Multiple command and receive MULTICMDRCV - -
Multiple command and send MULTICMDSND - -
18.17.1 Functionality
M14790-3 v5
The IED provides two function blocks enabling several IEDs to send and receive signals via the
interbay bus. The sending function block, MULTICMDSND, takes 16 binary inputs. LON enables
these to be transmitted to the equivalent receiving function block, MULTICMDRCV, which has 16
binary outputs.
18.17.2 Design
SEMOD119958-1 v1
18.17.2.1 General
M14792-3 v3
The common behavior for all 16 outputs of the MULTICMDRCV is set to either of two modes:
Steady or Pulse.
1 = Steady: This mode simply forwards the received signals to the binary outputs.
2 = Pulse: When a received signal transitions from 0 (zero) to 1 (one), a pulse with a duration of
exactly one execution cycle is triggered on the corresponding binary output. This means that
no connected function block may have a cycle time that is higher than the execution cycle time
of the particular MULTICMDRCV instance.
1MRK 502 066-UUS B Section 18
Station communication
1205
Technical manual