EasyManua.ls Logo

ABB Relion 670 series - Page 1221

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Values (Range) Unit Step Default Description
CommSync Slave
Master
- - Slave Com Synchronization mode of LDCM,
0=Slave, 1=Master
OptoPower LowPower
HighPower
- - LowPower Transmission power for LDCM, 0=Low,
1=High
TransmCurr CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
- - CT-GRP1 Summation mode for transmitted current
values
ComFailAlrmDel 5 - 500 ms 5 100 Time delay before communication error
signal is activated
ComFailResDel 5 - 500 ms 5 100 Reset delay before communication error
signal is reset
RedChSwTime 5 - 500 ms 5 5 Time delay before switching in redundant
channel
RedChRturnTime 5 - 500 ms 5 100 Time delay before switching back from
redundant channel
AsymDelay -20.00 - 20.00 ms 0.01 0.00 Asymmetric delay when communication
use echo synch.
AnalogLatency 2 - 20 - 1 2 Latency between local analogue data and
transmitted
remAinLatency 2 - 20 - 1 2 Analog latency of remote terminal
MaxTransmDelay 0 - 40 ms 1 20 Max allowed transmission delay
CompRange 0-10kA
0-25kA
0-50kA
0-150kA
- - 0-25kA Compression range
MaxtDiffLevel 200 - 2000 us 1 600 Maximum time diff for ECHO back-up
DeadbandtDiff 200 - 1000 us 1 300 Deadband for t Diff
InvertPolX21 Disabled
Enabled
- - Disabled Invert polarization for X21 communication
PID-3874-SETTINGS v5
Table 936: LDCMRecBinStat3 Non group settings (basic)
Name Values (Range) Unit Step Default Description
ChannelMode Blocked
Normal
OutOfService
- - Normal Channel mode of LDCM, 0=OFF, 1=ON,
2=OutOfService
TerminalNo 0 - 255 - 1 0 Terminal number used for line differential
communication
RemoteTermNo 0 - 255 - 1 0 Terminal number on remote terminal
DiffSync Echo
GPS
- - Echo Diff Synchronization mode of LDCM,
0=ECHO, 1=GPS
GPSSyncErr Block
Echo
- - Block Operation mode when GPS synchroniation
signal is lost
CommSync Slave
Master
- - Slave Com Synchronization mode of LDCM,
0=Slave, 1=Master
Table continues on next page
1MRK 502 066-UUS B Section 19
Remote communication
1215
Technical manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals