Name Values (Range) Unit Step Default Description
OptoPower LowPower
HighPower
- - LowPower Transmission power for LDCM, 0=Low,
1=High
TransmCurr CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
RedundantChann
el
- - CT-GRP1 Summation mode for transmitted current
values
ComFailAlrmDel 5 - 500 ms 5 100 Time delay before communication error
signal is activated
ComFailResDel 5 - 500 ms 5 100 Reset delay before communication error
signal is reset
RedChSwTime 5 - 500 ms 5 5 Time delay before switching in redundant
channel
RedChRturnTime 5 - 500 ms 5 100 Time delay before switching back from
redundant channel
AsymDelay -20.00 - 20.00 ms 0.01 0.00 Asymmetric delay when communication
use echo synch.
AnalogLatency 2 - 20 - 1 2 Latency between local analogue data and
transmitted
remAinLatency 2 - 20 - 1 2 Analog latency of remote terminal
MaxTransmDelay 0 - 40 ms 1 20 Max allowed transmission delay
CompRange 0-10kA
0-25kA
0-50kA
0-150kA
- - 0-25kA Compression range
MaxtDiffLevel 200 - 2000 us 1 600 Maximum time diff for ECHO back-up
DeadbandtDiff 200 - 1000 us 1 300 Deadband for t Diff
InvertPolX21 Disabled
Enabled
- - Disabled Invert polarization for X21 communication
19.1.6 Monitored data
PID-3872-MONITOREDDATA v4
Table 937: LDCMRecBinStat1 Monitored data
Name Type Values (Range) Unit Description
CommStatus BOOLEAN 0=Ok
1=SyncErr
2=No RXD
3=LocalGPSErr
4=RemGPSErr
5=LocAndRemG
PSErr
6=LocalADErr
7=RemADErr
8=LocAndRemA
DErr
9=AddressErr
10=FreqConfErr
11=LatencyConf
Err
- Status of communication link
Section 19 1MRK 502 066-UUS B
Remote communication
1216
Technical manual

Table of Contents