PID-3966-SETTINGS v5
Table 960: TIMESYNCHGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
CoarseSyncSrc Disabled
SPA
LON
SNTP
DNP
IEC103
- - Disabled Coarse time synchronization source
FineSyncSource Disabled
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
- - Disabled Fine time synchronization source
SyncMaster Disabled
SNTP-Server
- - Disabled Activate IEDas synchronization master
TimeAdjustRate Slow
Fast
- - Fast Adjust rate for time synchronization
HWSyncSrc Disabled
GPS
IRIG-B
PPS
- - Disabled Hardware time synchronization source
AppSynch NoSynch
Synch
- - NoSynch Time synchronization mode for application
SyncAccLevel Class T5 (1us)
Class T4 (4us)
Unspecified
- - Unspecified Wanted time synchronization accuracy
PID-6188-SETTINGS v4
Table 961: BININPUT Non group settings (basic)
Name Values (Range) Unit Step Default Description
ModulePosition 3 - 16 - 1 3 Hardware position of IO module for time
synchronization
BinaryInput 1 - 16 - 1 1 Binary input number for time
synchronization
BinDetection PositiveEdge
NegativeEdge
- - PositiveEdge Positive or negative edge detection