21.2 Parameter setting groups
IP1745-1 v1
21.2.1 Functionality
M12006-6 v7
Use the six different groups of settings to optimize the IED operation for different power system
conditions. Creating and switching between fine-tuned setting sets, either from the local HMI or
configurable binary inputs, results in a highly adaptable IED that can be applied to a variety of
power system scenarios.
21.2.2 Function block
IP9661-1 v1
M12010-3 v3
ANSI05000433-2-en.vsd
ActiveGroup
ACTGRP1
ACTGRP2
ACTGRP3
ACTGRP4
ACTGRP5
ACTGRP6
GRP1
GRP2
GRP3
GRP4
GRP5
GRP6
GRP_CHGD
ANSI05000433 V2 EN-US
Figure 632: ActiveGroup function block
21.2.3 Signals
IP14073-1 v2
PID-6558-INPUTSIGNALS v4
Table 969: ACTVGRP Input signals
Name Type Default Description
ACTGRP1 BOOLEAN 0 Selects setting group 1 as active
ACTGRP2 BOOLEAN 0 Selects setting group 2 as active
ACTGRP3 BOOLEAN 0 Selects setting group 3 as active
ACTGRP4 BOOLEAN 0 Selects setting group 4 as active
ACTGRP5 BOOLEAN 0 Selects setting group 5 as active
ACTGRP6 BOOLEAN 0 Selects setting group 6 as active
PID-6558-OUTPUTSIGNALS v4
Table 970: ACTVGRP Output signals
Name Type Description
GRP1 BOOLEAN Setting group 1 is active
GRP2 BOOLEAN Setting group 2 is active
GRP3 BOOLEAN Setting group 3 is active
GRP4 BOOLEAN Setting group 4 is active
GRP5 BOOLEAN Setting group 5 is active
GRP6 BOOLEAN Setting group 6 is active
GRP_CHGD BOOLEAN Pulse when setting changed
REMSETEN BOOLEAN Settings over IEC 61850 enabled
1MRK 502 066-UUS B Section 21
Basic IED functions
1253
Technical manual