Name Type Values (Range) Unit Description
BO19 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 19 status
BO20VALUE BOOLEAN 1=1
0=0
- Binary output 20 value
BO20FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 20 force
BO20 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 20 status
BO21VALUE BOOLEAN 1=1
0=0
- Binary output 21 value
BO21FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 21 force
BO21 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 21 status
BO22VALUE BOOLEAN 1=1
0=0
- Binary output 22 value
BO22FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 22 force
BO22 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 22 status
BO23VALUE BOOLEAN 1=1
0=0
- Binary output 23 value
BO23FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 23 force
BO23 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 23 status
BO24VALUE BOOLEAN 1=1
0=0
- Binary output 24 value
BO24FORCE BOOLEAN 0=Normal
1=Forced
- nary output 24 force
BO24 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 24 status
22.2.8.6 Technical data
SEMOD55355-1 v1
M12441-1 v10
Table 1015:BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity
Trip and Signal relays
Binary outputs 24
Max system voltage 250 V AC, DC
Min load voltage 24VDC
Test voltage across open contact, 1 min 1000 V rms
Table continues on next page
Section 22 1MRK 502 066-UUS B
IED hardware
1300
Technical manual