Name Type Values (Range) Unit Description
BO10VALUE BOOLEAN 1=1
0=0
- Binary output 10 value
BO10FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 10 force
BO10 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 10 status
BO11VALUE BOOLEAN 1=1
0=0
- Binary output 11 value
BO11FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 11 force
BO11 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 11 status
BO12VALUE BOOLEAN 1=1
0=0
- Binary output 12 value
BO12FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 12 force
BO12 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 12 status
22.2.9.6 Technical data
SEMOD175396-1 v1
SEMOD175395-2 v9
Table
1020:
SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Function of quantity Static binary output trip
Rated voltage 48-60 VDC 110-250 VDC
Number of outputs 6 6
Impedance open state ~300 kΩ ~810 kΩ
Test voltage across open contact, 1
min
No galvanic separation No galvanic separation
Current carrying capacity:
Continuous 5 A 5 A
1.0 s 10 A 10 A
Making capacity at capacitive load with
the maximum capacitance of 0.2 μF :
0.2 s 30 A 30 A
1.0 s 10 A 10 A
Breaking capacity for DC with L/R ≤ 40
ms
48 V/1 A 110 V/0.4 A
60 V/0.75 A 125 V/0.35 A
Table continues on next page
1MRK 502 066-UUS B Section 22
IED hardware
1305
Technical manual