22.2.10.4 Settings
PID-4050-SETTINGS v2
Table 1024:IOMIN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Enabled Binary input/output module in operation
(On) or not (Off)
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit
22.2.10.5 Monitored data
PID-4050-MONITOREDDATA v2
Table 1025:IOMIN Monitored data
Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
- Binary input part of IOM module status
PID-4049-MONITOREDDATA v2
Table 1026:IOMOUT Monitored data
Name Type Values (Range) Unit Description
BO1VALUE BOOLEAN 1=1
0=0
- Binary output 1 value
BO1FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 1 force
BO1 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 1 status
BO2VALUE BOOLEAN 1=1
0=0
- Binary output 2 value
BO2FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 2 force
BO2 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 2 status
BO3VALUE BOOLEAN 1=1
0=0
- Binary output 3 value
BO3FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 3 force
BO3 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 3 status
BO4VALUE BOOLEAN 1=1
0=0
- Binary output 4 value
BO4FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 4 force
Table continues on next page
Section 22 1MRK 502 066-UUS B
IED hardware
1310
Technical manual