EasyManua.ls Logo

ABB Relion 670 series - Page 1318

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Type Values (Range) Unit Description
BO11 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 11 status
BO12VALUE BOOLEAN 1=1
0=0
- Binary output 12 value
BO12FORCE BOOLEAN 0=Normal
1=Forced
- Binary output 12 force
BO12 BOOLEAN 0=Normal
1=Forced
2=Blocked
- Binary output 12 status
22.2.10.6 Technical data
IP10636-1 v1
M12573-1 v8.1.1
Table 1027:IOM - Binary input/output module
Quantity Rated value Nominal range
Binary inputs 8 -
DC voltage, RL 24/30 V
48/60 V
125 V
220/250 V
RL ±20%
RL ±20%
RL ±20%
RL ±20%
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
-
Counter input frequency 10 pulses/s max
Oscillating signal discriminator Blocking settable 1-40 Hz
Release settable 1-30 Hz
Debounce filter Settable 1-20 ms
Binary input operate time
(Debounce filter set to 0 ms)
3 ms -
Maximum 176 binary input channels may be activated simultaneously with
influencing factors within nominal range.
The stated operate time for functions include the operating time for the binary
inputs and outputs.
Section 22 1MRK 502 066-UUS B