22.2.11.5 Monitored data
PID-4110-MONITOREDDATA v4
Table 1033:MIM Monitored data
Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
- Milliampere input module status
CH1 REAL - - Analog input 1
CH2 REAL - - Analog input 2
CH3 REAL - - Analog input 3
CH4 REAL - - Analog input 4
CH5 REAL - - Analog input 5
CH6 REAL - - Analog input 6
CH1 REAL - A Service value analog input 1
CH2 REAL - A Service value analog input 2
CH3 REAL - A Service value analog input 3
CH4 REAL - A Service value analog input 4
CH5 REAL - A Service value analog input 5
CH6 REAL - A Service value analog input 6
22.2.11.6 Technical data
SEMOD55438-1 v1
M6389-1 v4
Table
1034:
MIM - mA input module
Quantity: Rated value: Nominal range:
Input resistance R
in
= 194 Ohm -
Input range ±5, ±10, ±20mA
0-5, 0-10, 0-20, 4-20mA
-
Power consumption
each mA-board
each mA input
£ 2 W
£ 0.1 W
-
22.2.12 Serial and LON communication module (SLM)
IP15583-1 v2
22.2.12.1 Introduction
M14933-3 v4
The serial and LON communication module (SLM) is used for SPA, IEC 60870-5-103, DNP3 and LON
communication. The module has two optical communication ports for plastic/plastic, plastic/
glass or glass/glass. One port is used for serial communication (SPA, IEC 60870-5-103 and DNP3
port) and one port is dedicated for LON communication.
1MRK 502 066-UUS B Section 22
IED hardware
1319
Technical manual