Quantity Rated value
Amplitude modulated
– low level
– high level
1-3 Vpp
3 x low level, max 9 Vpp
Supported formats IRIG-B 00x, IRIG-B 12x
Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Input impedance 100 k ohm
Optical connector:
Optical connector IRIG-B Type ST
Type of fiber 62.5/125 μm multimode fiber
Supported formats IRIG-B 00x
Accuracy +/- 1μs
22.3 Dimensions
IP11490-1 v3
22.3.1 Case without rear cover
SEMOD53195-1 v1
M2152-3 v5
C
B
D
E
A
IEC08000164-2-en.vsd
IEC08000164 V2 EN-US
Figure 670: Case without rear cover