PID-3545-OUTPUTSIGNALS v4
Table 84: ZDRDIR (21D) Output signals
Name Type Description
STDIRCND INTEGER Binary coded directional information per measuring loop
7.1.5 Settings
GUID-62142086-79A9-46FF-A14F-BA0CDD6B6466 v1
Signals and settings for ZMQPDIS are valid for zone 1 while signals and settings for
ZMQAPDIS are valid for zone 2 - 5
PID-3651-SETTINGS v5
Table 85: ZMQPDIS (21) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
OperationDir Non-directional
Forward
Reverse
- - Forward Operation mode of directionality NonDir /
Forw / Rev
X1 0.10 - 3000.00 Ohm/p 0.01 30.00 Positive sequence reactance reach
R1 0.01 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.10 - 9000.00 Ohm/p 0.01 100.00 Zero sequence reactance reach
R0 0.01 - 3000.00 Ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPP 0.10 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach in ohm/loop, Ph-Ph
RFPG 0.10 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-G
OperationPP Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Phase-
Phase loops
OpModetPP Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Zone
timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPG Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Phase-
Ground loops
OpModetPG Disabled
Enabled
- - Enabled Operation mode Disable/ Enable of Zone
timer, Ph-G
tPG 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-G
IMinPUPP 10 - 1000 %IB 1 20 Minimum operate delta current for Phase-
Phase loops
IMinPUPG 10 - 1000 %IB 1 20 Minimum pickup phase current for Phase-
to-ground loops
IMinOpIR 5 - 1000 %IB 1 5 Minimum operate residual current for
Phase-Ground loops
1MRK 502 066-UUS B Section 7
Impedance protection
181
Technical manual