Table 86: ZMQPDIS (21) Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
PID-3650-SETTINGS v5
Table 87: ZMQAPDIS (21) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
OperationDir Non-directional
Forward
Reverse
- - Forward Operation mode of directionality NonDir /
Forw / Rev
X1 0.10 - 3000.00 Ohm/p 0.01 40.00 Positive sequence reactance reach
R1 0.01 - 1000.00 Ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.10 - 9000.00 Ohm/p 0.01 120.00 Zero sequence reactance reach
R0 0.01 - 3000.00 Ohm/p 0.01 15.00 Zero seq. resistance for zone
characteristic angle
RFPP 0.10 - 3000.00 Ohm/l 0.01 30.00 Fault resistance reach in ohm/loop, Ph-Ph
RFPG 0.10 - 9000.00 Ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-G
OperationPP Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Phase-
Phase loops
OpModetPP Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Zone
timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPG Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Phase-
Ground loops
OpModetPG Disabled
Enabled
- - Enabled Operation mode Disable/ Enable of Zone
timer, Ph-G
tPG 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-G
IMinPUPP 10 - 1000 %IB 1 20 Minimum operate delta current for Phase-
Phase loops
IMinPUPG 10 - 1000 %IB 1 20 Minimum pickup phase current for Phase-
to-ground loops
Table 88: ZMQAPDIS (21) Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Section 7 1MRK 502 066-UUS B
Impedance protection
182