7.7.7 Technical data
GUID-9E13C38A-3B6D-402B-98A6-6CDA20632CE7 v4
Table 139: FRPSPDIS (21) technical data
Function Range or value Accuracy
(5-500)% of IBase ±1.0% of I
n
at I ≤ I
n
±1.0% of I at I > I
n
Reactive reach, positive
sequence
(0.50–3000.00) Ω/phase ±2.0% static accuracy
±2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x V
n
Current range: (0.5-30) x I
n
Angle: at 0 degrees and 85 degrees
Resistive reach, positive
sequence
(0.10–1000.00) Ω/phase
Reactive reach, zero sequence (0.50–9000.00) Ω/phase
Resistive reach, zero sequence (0.50–3000.00) Ω/phase
Fault resistance, phase-to-
ground faults, forward and
reverse
(1.00–9000.00) Ω/loop
Fault resistance, Ph-Ph faults,
forward and reverse
(0.50–3000.00) Ω/loop
Load encroachment criteria:
Load resistance, forward and
reverse
Safety load impedance angle
(1.00–3000.00) Ω/phase
(5-70) degrees
Reset ratio 105% typically -
7.8 High speed distance protection ZMFPDIS (21)
GUID-CC4F7338-2281-411D-B55A-67BF03F31681 v3
7.8.1 Identification
GUID-8ACD3565-C607-4399-89D2-A05657840E6D v3
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
High speed distance protection zone ZMFPDIS
S00346 V1 EN-US
21
7.8.2 Functionality
GUID-2E34AB7F-886E-499F-8984-09041A89238D v6
The ZMFPDIS function is a six zone full scheme protection with three fault loops for phase-to-
phase faults and three fault loops for phase-to-ground faults for each of the independent zones,
which makes the function suitable in applications with single-phase autoreclosing.
In each measurement zone, ZMFPDIS function is designed with the flexibility to operate in either
quadrilateral or mho characteristic mode for separate phase-to-earth or phase-to-phase loops.
1MRK 502 066-UUS B Section 7
Impedance protection
291
Technical manual