Figure 157: Simplified offset mho characteristic and vector diagram for phase A-to-ground
fault
Operation occurs if 90°≤β≤270°.
Offset mho
GUID-B1EF3931-7B86-4C7B-BCEA-3034482BA240 v1
The condition for operation of offset mho at phase-to-earth fault is that the angle β between the
two compensated voltages is equal to or greater than 90°, see figure
158. The angle will be 90° for
fault location on the boundary of the circle.
β
= +
( )
+
)
{
arg ( ) ( ]V I I K Z V I I K Z
A A N set A A N RVset
3 0 1 3 0 1arg
}}
ANSIEQUATION15022 V1 EN-US (Equation 92)
where
Z RVset1
is the complex positive sequence impedance of the line in Ω/
phase for phase-to-ground fault opposite to zone direction and
is defined as,
1MRK 502 066-UUS B Section 7
Impedance protection
315
Technical manual