EasyManua.ls Logo

ABB Relion 670 series - Page 361

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A
V
3 0 1
N set
I K Z
( 3 0 ) 1
comp A A N set
V V I I K Z
pol
V
IAR
IAjX
1
A set
IZ
ANSI15000059-1-en.vsdx
ANSI15000059 V1 EN-US
Figure 180: Simplified offset mho characteristic and vector diagram for phase A-to-ground
fault
Operation occurs if 90 °≤β≤270 °.
Offset mho
GUID-1CD62635-A76A-41F7-A814-8BB493F5B051 v1
The condition for operation of offset mho at phase-to-earth fault is that the angle β between the
two compensated voltages is equal to or greater than 90°, see figure
181. The angle will be 90° for
fault location on the boundary of the circle.
β
= +
( )
+
)
{
arg ( ) ( ]V I I K Z V I I K Z
A A N set A A N RVset
3 0 1 3 0 1arg
}}
ANSIEQUATION15022 V1 EN-US (Equation 107)
where
Z RVset1
is the complex positive sequence impedance of the line in Ω/
phase for phase-to-ground fault opposite to zone direction and
is defined as,
Z R RvPEZx j X RvPEZx
RVset
1 1 1= +
IECEQUATION15023 V1 EN-US (Equation 108)
1MRK 502 066-UUS B Section 7
Impedance protection
355
Technical manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals