EasyManua.ls Logo

ABB Relion 670 series - Page 370

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Cyclic reporting
SEMOD54417-158 v3
The cyclic reporting of measured value is performed according to chosen setting (
XRepTyp
). The
measuring channel reports the value independent of magnitude or integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when measured value
passes any of the defined threshold limits.
IEC05000500-2-en.vsdx
Value
1
Y
t
Value
2
Value
3
Value
4
Value Reported
(1st)
Value Reported
Value
5
Value Reported
Y1
Y2
Y5
Value Reported
Value Reported
Y3
Y4
(*)Set value for t: XDbRepInt
t (*) t (*) t (*) t (*)
IEC05000500 V2 EN-US
Figure 191: Periodic reporting
Magnitude dead-band supervision
SEMOD54417-163 v5
If a measuring value is changed, compared to the last reported value, and the change is larger than
the ±ΔY pre-defined limits that are set by user (
UDbRepIn
), then the measuring channel reports
the new value to a higher level. This limits the information flow to a minimum necessary.
Figure
192 shows an example with the magnitude dead-band supervision. The picture is simplified:
the process is not continuous but the values are evaluated with a time interval of one execution
cycle from each other.
Section 7 1MRK 502 066-UUS B
Impedance protection
364
Technical manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals