Cyclic reporting
SEMOD54417-158 v3
The cyclic reporting of measured value is performed according to chosen setting (
XRepTyp
). The
measuring channel reports the value independent of magnitude or integral dead-band reporting.
In addition to the normal cyclic reporting the IED also report spontaneously when measured value
passes any of the defined threshold limits.
IEC05000500-2-en.vsdx
Value
1
Y
t
Value
2
Value
3
Value
4
Value Reported
(1st)
Value Reported
Value
5
Value Reported
Y1
Y2
Y5
Value Reported
Value Reported
Y3
Y4
(*)Set value for t: XDbRepInt
t (*) t (*) t (*) t (*)
IEC05000500 V2 EN-US
Figure 191: Periodic reporting
Magnitude dead-band supervision
SEMOD54417-163 v5
If a measuring value is changed, compared to the last reported value, and the change is larger than
the ±ΔY pre-defined limits that are set by user (
UDbRepIn
), then the measuring channel reports
the new value to a higher level. This limits the information flow to a minimum necessary.
Figure
192 shows an example with the magnitude dead-band supervision. The picture is simplified:
the process is not continuous but the values are evaluated with a time interval of one execution
cycle from each other.