Figure 236: Block diagram of ZGVPDIS
7.15.7.1 Operation principle of zone 1
GUID-994DD2FC-3B69-4ED6-AB94-A0C0D4399637 v3
In general, the zone 1 must cover the generator winding, the cables or busbars and step up
transformer.
Under impedance functionality is provided as selective protection for the phase-to-phase faults in
zone 1. Hence the functionality of zone 1 includes only phase-to-phase measuring loops.
Zone 1 functionality can be set to
PP Loops
or
Disabled
using the setting
OpModeZ1
.
Figure 237 shows the functionality of zone 1.