Figure 240: Logic diagram for the selection of the maximum current loop
The phase-to-ground voltage is compensated with zero sequence voltage in order to avoid the
function operating for ground faults in zone 1, that is, complete generator stator winding and LV
winding of the power transformer.
The reach settings for zone 2 can be provided using the
Z2Fwd
,
Z2Rev
and
ImpedanceAng
settings. The
Z2Fwd
is forward reach setting and
Z2Rev
is reverse reach setting. The offset mho
characteristic for phase-to-ground loop is shown in Figure 241. The offset mho characteristics for
phase-to-phase loop is shown in Figure
242.
1 0 2Vcomp V AG V I A Z FW= - - ×
2 0 2Vcomp V AG V I A Z REV= - + ×
ANSI11000299 V1 EN-US
Figure 241: Simplified offset mho characteristics for A-to-G fault in zone 2
Section 7 1MRK 502 066-UUS B
Impedance protection
442
Technical manual