Name Values (Range) Unit Step Default Description
tReset4 0.000 - 60.000 s 0.001 0.020 Constant reset time for step 4
tPCrv4 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 4
tACrv4 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 4
tBCrv4 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 4
tCCrv4 0.1 - 10.0 - 0.1 1.0 Parameter C for customer programmable
curve for step 4
tPRCrv4 0.005 - 3.000 - 0.001 0.500 Parameter PR for customer programmable
curve for step 4
tTRCrv4 0.005 - 100.000 - 0.001 13.500 Parameter TR for customer programmable
curve for step 4
tCRCrv4 0.1 - 10.0 - 0.1 1.0 Parameter CR for customer programmable
curve for step 4
HarmBlock4 Disabled
Enabled
- - Disabled Enable block of step 4 from harmonic
restrain
Table 216: OC4PTOC (51_67) Non group settings (basic)
Name Values (Range) Unit Step Default Description
MeasType DFT
RMS
- - DFT Selection between DFT and RMS
measurement
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Table 217: OC4PTOC (51_67) Non group settings (advanced)
Name Values (Range) Unit Step Default Description
PU1_MinEd2Set 5 - 2500 %IB 1 5 Minimum settable operating phase current
level for step 1 in % of IBase, for 61850 Ed.2
settings
PU1_MaxEd2Set 5 - 2500 %IB 1 2500 Maximum settable operating phase
current level for step 1 in % of IBase, for
61850 Ed.2 settings
PU2_MinEd2Set 5 - 2500 %IB 1 5 Minimum settable operating phase current
level for step 2 in % of IBase, for 61850
Ed.2 settings
PU2_MaxEd2Set 5 - 2500 %IB 1 2500 Maximum settable operating phase
current level for step 2 in % of IBase, for
61850 Ed.2 settings
PU3_MinEd2Set 5 - 2500 %IB 1 5 Minimum settable operating phase current
level for step 3 in % of IBase, for 61850
Ed.2 settings
Table continues on next page
Section 8 1MRK 502 066-UUS B
Current protection
458