Figure 263: Simplified logic diagram for directional supervision element with integrated directional
comparison step
8.5.8 Technical data
GUID-10E9194D-3AE9-4D0F-867E-473E6F4BF443 v1
GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v5
Table 241: NS4PTOC (46I2) technical data
Function Range or value Accuracy
Trip value, step 1 - 4 (1-2500)% of
lBase
±1.0% of I
n
at I £ I
n
±1.0% of I at I > I
n
Reset ratio > 95% at (10-2500)% of
IBase
-
Independent time delay at 0
to 2 x I
set
, step 1 - 4
(0.000-60.000) s ±0.2% or ±35 ms whichever is
greater
Minimum operate time for
inverse curves, step 1 - 4
(0.000 - 60.000) s ±0.2% or ±35 ms whichever is
greater
Inverse time characteristics,
see table 1076, table 1077
and table 1078
16 curve types See table 1076, table 1077 and
table 1078
Table continues on next page
1MRK 502 066-UUS B Section 8
Current protection
503
Technical manual