8.6.5 Settings
PID-3892-SETTINGS v6
Table 244: SDEPSDE (67N) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
OpModeSel 3I0Cosfi
3I03V0Cosfi
3I0 and fi
- - 3I0Cosfi Selection of operation mode for
protection
DirMode Forward
Reverse
- - Forward Direction of operation forward or reverse
RCADir -179 - 180 Deg 1 -90 Relay characteristic angle RCA, in deg
RCAComp -10.0 - 10.0 Deg 0.1 0.0 Relay characteristic angle compensation
ROADir 0 - 90 Deg 1 90 Relay open angle ROA used as release in
phase mode, in deg
INCosPhiPU 0.25 - 200.00 %IB 0.01 1.00 Set level for 3I0cosFi, directional res over
current in % of IBase
SN_PU 0.25 - 200.00 %SB 0.01 10.00 Set level for 3I03U0cosFi, starting inv time
count in % of SBase
INDirPU 0.25 - 200.00 %IB 0.01 5.00 Set level for directional residual over
current prot in % of IBase
tDef 0.000 - 60.000 s 0.001 0.100 Definite time delay directional residual
overcurrent, in sec
SRef 0.03 - 200.00 %SB 0.01 10.00 Reference value of res power for inverse
time count in % of SBase
TDSN 0.00 - 2.00 - 0.01 0.10 Time multiplier setting for directional
residual power mode
OpINNonDir Disabled
Enabled
- - Disabled Operation of non-directional residual
overcurrent protection
INNonDirPU 1.00 - 400.00 %IB 0.01 10.00 Set level for non directional residual over
current in % of IBase
tINNonDir 0.000 - 60.000 s 0.001 1.000 Time delay for non-directional residual
over current, in sec
TimeChar ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
- - IEC Norm. inv. Operation curve selection for IDMT
operation
Table continues on next page
Section 8 1MRK 502 066-UUS B
Current protection
508
Technical manual