EasyManua.ls Logo

ABB Relion 670 series - Page 516

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.6.6 Monitored data
PID-3892-MONITOREDDATA v5
Table 248: SDEPSDE (67N) Monitored data
Name Type Values (Range) Unit Description
INCOSPHI REAL - A Magnitude of residual current along the
polarizing quantity 3I0cos(Fi-RCA)
IN REAL - A Measured magnitude of the residual
current 3I0
VN REAL - kV Measured magnitude of the residual
voltage 3V0
SN REAL - MVA Measured magnitude of residual power
3I03V0cos(Fi-RCA)
ANG FI-RCA REAL - deg Angle between 3V0 and 3I0 minus RCA (Fi-
RCA)
8.6.7 Operation principle
8.6.7.1 Function inputs
SEMOD171963-4 v4
The function is using phasors of the residual current and voltage. Group signals I3P and V3P
containing phasors of residual current and voltage are taken from pre-processor blocks.
The sensitive directional ground fault protection has the following sub-functions included:
Directional residual current protection measuring 3I
0
·cos φ
SEMOD171963-8 v7
φ is defined as the angle between the residual current 3I
0
and the reference voltage (|φ=ang(3I
0
)-
ang(V
ref
)|). The reference voltage (Vref) is the polarizing quantity which is used for directionality
and is defined as Vref = -3V
0
e
—jRCADir
, that is -3V
0
inversely rotated by the set characteristic angle
RCADir
.
RCADir
is normally set equal to 0 in a high impedance grounded network with a neutral
point resistor as the active current component is appearing out on the faulted feeder only.
RCADir
is set equal to -90° in an isolated network as all currents are mainly capacitive. The function
operates when 3I
0
·cos φ gets larger than the set value.
Section 8 1MRK 502 066-UUS B
Current protection
510
Technical manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals