8.8.8 Technical data
IP10269-1 v1
M12353-1 v13
Table 262: CCRBRF (50BF) technical data
Function Range or value Accuracy
Trip phase current (5-200)% of
lBase
±1.0% of I
n
at I £ I
n
±1.0% of I at I > I
n
Reset ratio, phase current > 95% -
Trip residual current (2-200)% of
lBase
±1.0% of I
n
at I £ I
n
±1.0% of I at I > I
n
Reset ratio, residual current > 95% -
Phase current pickup for blocking of contact
function
(5-200)% of
lBase
±1.0% of I
n
at I £ I
n
±1.0% of I at I > I
n
Reset ratio > 95% -
Trip time for current detection 10 ms typically -
Reset time for current detection 15 ms maximum -
Time delay for re-trip at 0 to 2 x I
set
(0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Time delay for back-up trip at 0 to 2 x I
set
(0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Time delay for back-up trip at multi-phase
pickup at 0 to 2 x I
set
(0.000-60.000) s ±0.2% or ±20 ms whichever is greater
Additional time delay for a second back-up
trip at 0 to 2 x I
set
(0.000-60.000) s ±0.2% or ±20 ms whichever is greater
Time delay for alarm for faulty circuit breaker (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
8.9 Stub protection STBPTOC (50STB)
IP14515-1 v3
8.9.1 Identification
M17108-1 v2
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Stub protection STBPTOC
SYMBOL-T V1 EN-US
50STB
8.9.2 Functionality
M12902-3 v9
When a power line is taken out of service for maintenance and the line disconnector is opened in
multi-breaker arrangements the voltage transformers will mostly be outside on the disconnected
part. The primary line distance protection will thus not be able to trip and must be blocked.