Table 287: GOPPDOP (32) Group settings (advanced)
Name Values (Range) Unit Step Default Description
k 0.000 - 0.999 - 0.001 0.000 Low pass filter coefficient for power
measurement, P and Q
Hysteresis1 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 1 in % of
SBase
Hysteresis2 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 2 in % of
SBase
IMagComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates current
error at 5% of Ir
IMagComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates current
error at 30% of Ir
IMagComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates current
error at 100% of Ir
VMagComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 5% of Ur
VMagComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 30% of Ur
VMagComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 100% of Ur
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 100% of Ir
Table 288: GOPPDOP (32) Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Mode A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
- - Pos Seq Selection of measured current and voltage
1MRK 502 066-UUS B Section 8
Current protection
553
Technical manual