characteristic Trip logic
Alarm Ripple
Detection
block
block
Undercurrent
protection for rotor
winding
block
IEC12000016-1-en.vsd
IEC12000016 V1 EN-US
Figure 316: Representation of the rotor overload protection
Each of these five sub-blocks will be described in the following sections of this document.
Current measurement
Three phase currents are measured either on the high voltage side (HV) or on the low voltage side
(LV) of the excitation transformer, see Figure
317.
Section 8 1MRK 502 066-UUS B
Current protection
590
Technical manual