Function Range or value Accuracy
Start time, undercurrent at 2
to 0 x I
set
Min = 15 ms
Max = 30 ms
Independent time delay for
undercurrent function at 2 to 0
x I
set
(0.0–600.0) s ±0.2% or ±45 ms whichever is greater