Table 337: UV2PTUV (27) Non group settings (basic)
Name Values (Range) Unit Step Default Description
ConnType PhN DFT
PhPh RMS
PhN RMS
PhPh DFT
- - PhN DFT Group selector for connection type
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
9.1.6 Monitored data
PID-3586-MONITOREDDATA v5
Table 338: UV2PTUV (27) Monitored data
Name Type Values (Range) Unit Description
VA REAL - kV Voltage in phase A
VB REAL - kV Voltage in phase B
VC REAL - kV Voltage in phase C
9.1.7 Operation principle
M15326-3 v8
Two-step undervoltage protection (UV2PTUV ,27) is used to detect low power system voltage.
UV2PTUV (27) has two voltage measuring steps with separate time delays. If one, two or three
phase voltages decrease below the set value, a corresponding PICKUP signal is generated.
UV2PTUV (27) can be set to PICKUP/TRIP based on
1 out of 3
,
2 out of 3
or
3 out of 3
of the
measured voltages, being below the set point. If the voltage remains below the set value for a time
period corresponding to the chosen time delay, the corresponding trip signal is issued. To avoid
an unwanted trip due to disconnection of the related high voltage equipment, a voltage controlled
blocking of the function is available, that is, if the voltage is lower than the set blocking level the
function is blocked and no PICKUP or TRIP signal is generated.The time delay characteristic is
individually chosen for each step and can be either definite time delay or inverse time delay.
UV2PTUV (27) can be set to measure phase-to-ground fundamental value, phase-to-phase
fundamental value, phase-to-ground true RMS value or phase-to-phase true RMS value. The choice
of the measuring is done by the parameter
ConnType
. The voltage related settings are made in
percent of base voltage which is set in kV phase-to-phase voltage. This means operation for
phase-to-ground voltage under:
(%) ( )
3
Vpickup VBase kV< ×
EQUATION1606 V1 EN-US (Equation 168)
and operation for phase-to-phase voltage under:
EQUATION1991-ANSI V1 EN-US (Equation 169)
1MRK 502 066-UUS B Section 9
Voltage protection
603