EasyManua.ls Logo

ABB Relion 670 series - Page 619

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9.2.3 Function block
M13803-3 v6
ANSI06000277-2-en.vsd
OV2PTOV (59)
V3P*
BLOCK
BLKTR1
BLK1
BLKTR2
BLK2
TRIP
TRST1
TRST1_A
TRST1_B
TRST1_C
TRST2
TRST2_A
TRST2_B
TRST2_C
PICKUP
PU_ST1
PU_ST1_A
PU_ST1_B
PU_ST1_C
PU_ST2
PU_ST2_A
PU_ST2_B
PU_ST2_C
ANSI06000277 V2 EN-US
Figure 331: OV2PTOV (59) function block
9.2.4 Signals
PID-3535-INPUTSIGNALS v6
Table 340: OV2PTOV (59) Input signals
Name Type Default Description
V3P GROUP
SIGNAL
- Group signal for three phase voltage input
BLOCK BOOLEAN 0 Block of function
BLKTR1 BOOLEAN 0 Block of trip signal, step 1
BLK1 BOOLEAN 0 Block of step 1
BLKTR2 BOOLEAN 0 Block of trip signal, step 2
BLK2 BOOLEAN 0 Block of step 2
PID-3535-OUTPUTSIGNALS v6
Table 341: OV2PTOV (59) Output signals
Name Type Description
TRIP BOOLEAN Trip
TRST1 BOOLEAN Common trip signal from step1
TRST1_A BOOLEAN Trip signal from step1 phase A
TRST1_B BOOLEAN Trip signal from step1 phase B
TRST1_C BOOLEAN Trip signal from step1 phase C
TRST2 BOOLEAN Common trip signal from step2
TRST2_A BOOLEAN Trip signal from step2 phase A
TRST2_B BOOLEAN Trip signal from step2 phase B
TRST2_C BOOLEAN Trip signal from step2 phase C
Table continues on next page
1MRK 502 066-UUS B Section 9
Voltage protection
613
Technical manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals