EasyManua.ls Logo

ABB Relion 670 series - Page 621

ABB Relion 670 series
1432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Values (Range) Unit Step Default Description
Pickup2 1.0 - 200.0 %VB 0.1 150.0 Voltage pickup value (Definite-Time &
Inverse-Time curve) in % of VBase, step 2
t2 0.000 - 60.000 s 0.001 5.000 Definitive time delay of step 2
t2Min 0.000 - 60.000 s 0.001 5.000 Minimum operate time for inverse curves
for step 2
TD2 0.05 - 1.10 - 0.01 0.05 Time multiplier for the inverse time delay
for step 2
HystAbs2 0.0 - 50.0 %VB 0.1 0.5 Absolute hysteresis in % of VBase, step 2
Table 343: OV2PTOV (59) Group settings (advanced)
Name Values (Range) Unit Step Default Description
tReset1 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite Time
curve step 1
ResetTypeCrv1 Instantaneous
Frozen timer
Linearly
decreased
- - Instantaneous Selection of used IDMT reset curve type for
step 1
tIReset1 0.000 - 60.000 s 0.001 0.025 Time delay in Inverse-Time reset (s), step 1
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for programmable over
voltage TOV curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Reset time delay used in IEC Definite Time
curve step 2
ResetTypeCrv2 Instantaneous
Frozen timer
Linearly
decreased
- - Instantaneous Selection of Time Delay reset curve for
step 2
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in Inverse-Time reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 2
Table continues on next page
1MRK 502 066-UUS B Section 9
Voltage protection
615
Technical manual

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals