Name Values (Range) Unit Step Default Description
ACrv1 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 1
BCrv1 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 1
CCrv1 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 1
DCrv1 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 1
PCrv1 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
CrvSat1 0 - 100 % 1 0 Tuning param for programmable over
voltage TOV curve, step 1
tReset2 0.000 - 60.000 s 0.001 0.025 Time delay in Definite-Time reset (s), step
2
ResetTypeCrv2 Instantaneous
Frozen timer
Linearly
decreased
- - Instantaneous Selection of Time Delay reset curve for
step 2
tIReset2 0.000 - 60.000 s 0.001 0.025 Time delay in Inverse-Time reset (s), step 2
ACrv2 0.005 - 200.000 - 0.001 1.000 Parameter A for customer programmable
curve for step 2
BCrv2 0.50 - 100.00 - 0.01 1.00 Parameter B for customer programmable
curve for step 2
CCrv2 0.0 - 1.0 - 0.1 0.0 Parameter C for customer programmable
curve for step 2
DCrv2 0.000 - 60.000 - 0.001 0.000 Parameter D for customer programmable
curve for step 2
PCrv2 0.000 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 2
CrvSat2 0 - 100 % 1 0 Tuning param for programmable over
voltage TOV curve, step 2
Table 351: ROV2PTOV (59N) Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
9.3.6 Monitored data
PID-3531-MONITOREDDATA v4
Table 352: ROV2PTOV (59N) Monitored data
Name
Type Values (Range) Unit Description
VLevel REAL - kV Magnitude of measured voltage
Section 9 1MRK 502 066-UUS B
Voltage protection
628