en05000835_ansi.vsd
RESTORE
Voltage
PICKUP
PICKUP
TRIP
Pickup
&
Trip
Output
Logic
BLOCK
Frequency
100 ms
Comparator
If
[PickupFreqGrad<0
AND
df/dt < PickupFreqGrad]
OR
[PickupFreqGrad>0
AND
df/dt > PickupFreqGrad]
Then
PICKUP
Comparator
V < IntBlockLevel
Comparator
f > RestoreFreq
OR
Time integrator
Definite Time Delay
TimeDlyOperate
TimeDlyReset
TimeDlyRestore
BLKDMAGN
Rate-of-Change
of Frequency
BLOCK
BLKTRIP
BLKRESET
ANSI05000835 V1 EN-US
Figure 367: Simplified logic diagram for SAPFRC (81)
10.3.8 Technical data
M14976-1 v10
Table 396: SAPFRC (81) Technical data
Function Range or value Accuracy
Trip value, pickup function (-10.00-10.00) Hz/s ±10.0 mHz/s
Trip value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz
Definite restore time delay (0.000-60.000) s ±0.2% or ±100 ms whichever is
greater
Definite time delay for frequency gradient trip (0.000-60.000) s ±0.2% or ±120 ms whichever is
greater
Definite reset time delay (0.000-60.000) s ±0.2% or ±250 ms whichever is
greater