Table 443: SESRSYN (25) Non group settings (basic)
Name Values (Range) Unit Step Default Description
SelPhaseBus1 Phase A
Phase B
Phase C
Phases AB
Phase BC
Phase CA
Positive sequence
- - Phase A Select phase for busbar1
GblBaseSelBus 1 - 12 - 1 1 Selection of one of the Global Base Value
groups, Bus
GblBaseSelLine 1 - 12 - 1 1 Selection of one of the Global Base Value
groups, Line
SelPhaseBus2 Phase A
Phase B
Phase C
Phases AB
Phase BC
Phase CA
Positive sequence
- - Phase A Select phase for busbar2
SelPhaseLine1 Phase A
Phase B
Phase C
Phases AB
Phase BC
Phase CA
Positive sequence
- - Phase A Select phase for line1
SelPhaseLine2 Phase A
Phase B
Phase C
Phases AB
Phase BC
Phase CA
Positive sequence
- - Phase A Select phase for line2
CBConfig No voltage sel.
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
- - No voltage sel. Select CB configuration
Table 444: SESRSYN (25) Non group settings (advanced)
Name Values (Range) Unit Step Default Description
PhaseShift -180 - 180 Deg 1 0 Additional phase angle for selected line
voltage
Section 14 1MRK 502 066-UUS B
Control
752
Technical manual