Name Values (Range) Unit Step Default Description
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
CT_WyePoint10 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec10 1 - 10 A 1 1 Rated CT secondary current
CTprim10 1 - 99999 A 1 3000 Rated CT primary current
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
3.5 Monitored data
PID-4153-MONITOREDDATA v4
Table 21: AISVBAS Monitored data
Name Type Values (Range) Unit Description
Status INTEGER 0=Ok
1=Error
2=AngRefLow
3=Uncorrelated
- Service value status
PID-3920-MONITOREDDATA v4
Table 22: TRM_12I Monitored data
Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
- Analog input module status
PID-3921-MONITOREDDATA v4
Table 23: TRM_6I_6U Monitored data
Name Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
- Analog input module status
PID-3922-MONITOREDDATA v4
Table 24: TRM_6I Monitored data
Name
Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
- Analog input module status
1MRK 502 066-UUS B Section 3
Analog inputs
77
Technical manual