Name Values (Range) Unit Step Default Description
UseParity Off
On
- - Off Enable parity check
tStable 1 - 60 s 1 2 Time after position change before the
value is accepted
CLFactor 1.0 - 3.0 - 0.1 2.0 Adjustable factor for contact life function
InitCLCounter 0 - 9999999 - 1 250000 CL counter start value
EnabTapCmd Off
On
- - On Enable commands to tap changer
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Table 536: TCMYLTC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
tTCTimeout 1 - 120 s 1 5 Tap changer constant time-out
tPulseDur 0.5 - 10.0 s 0.1 1.5 Raise/lower command output pulse
duration
PID-3668-SETTINGS v4
Table 537: TCLYLTC (84) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
tTCTimeout 1 - 120 s 1 5 Tap changer constant time-out
tPulseDur 0.5 - 10.0 s 0.1 1.5 Raise/lower command output pulse
duration
Table 538: TCLYLTC (84) Non group settings (basic)
Name Values (Range) Unit Step Default Description
LowVoltTap 1 - 63 - 1 1 Tap position for lowest voltage
HighVoltTap 1 - 63 - 1 33 Tap position for highest voltage
mALow 0.000 - 25.000 mA 0.001 4.000 mA for lowest voltage tap position
mAHigh 0.000 - 25.000 mA 0.001 20.000 mA for highest voltage tap position
CodeType BIN
BCD
Gray
SINGLE
mA
- - BIN Type of code conversion
UseParity Disabled
Enabled
- - Disabled Enable parity check
tStable 1 - 60 s 1 2 Time after position change before the
value is accepted
Table continues on next page