Name Values (Range) Unit Step Default Description
CLFactor 1.0 - 3.0 - 0.1 2.0 Adjustable factor for contact life function
InitCLCounter 0 - 9999999 s 1 250000 CL counter start value
EnabTapCmd Disabled
Enabled
- - Enabled Enable commands to tap changer
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
14.4.9 Monitored data
PID-6562-MONITOREDDATA v3
Table 539: TR1ATCC (90) Monitored data
Name Type Values (Range) Unit Description
BUSVOLT REAL - kV The average of the measured busbar
voltage (service value)
VOLTDEV REAL - % Voltage deviation compared to dead band
(%)
TRLDCURR REAL - A Amplitude of own load current
VSETOUT REAL - kV Voltage setpoint used in single mode
(service value)
VLOAD REAL - kV Calculated compensated voltage (service
value)
P REAL - MW Calculated active power (service value)
Q REAL - MVAr Calculated reactive power (service value)
IPRIM REAL - A Max of 3 phase currents (service value)
PID-6559-MONITOREDDATA v3
Table 540: TR8ATCC (90) Monitored data
Name Type Values (Range) Unit Description
BUSVOLT REAL - kV The average of the measured busbar
voltage (service value)
VOLTDEV REAL - % Voltage deviation compared to dead band
(%)
TRLDCURR REAL - A Amplitude of own load current
VSETOUT REAL - kV Voltage setpoint used in single mode
(service value)
VLOAD REAL - kV Calculated compensated voltage (service
value)
P REAL - MW Calculated active power (service value)
Q REAL - MVAr Calculated reactive power (service value)
IPRIM REAL - A Max of 3 phase currents (service value)
CCAVolt REAL - kV Circulating Current Adjusted Voltage
VSETPAR REAL - kV Average voltage setpoint used in parallel
mode
ICIRCUL REAL - A Circulating current
1MRK 502 066-UUS B Section 14
Control