Table 667: Truth table for RSMEMORYQT function block
RESET SET OUT NOUT
0 0 Last
value
Inverted last
value
0 1 1 0
1 0 0 1
1 1 0 1
15.7.8.1 Function block
GUID-BDBFD8BA-9253-4277-96D8-0FF7EE93B56E v1
RSMEMORYQT
SET
RESET
OUT
NOUT
IEC14000069-1-en.vsd
IEC14000069 V1 EN-US
Figure 509: RSMEMORYQT function block
15.7.8.2 Signals
GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1
PID-3812-INPUTSIGNALS v4
Table 668: RSMEMORYQT Input signals
Name Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset
PID-3812-OUTPUTSIGNALS v4
Table 669: RSMEMORYQT Output signals
Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal
15.7.8.3 Settings
PID-3812-SETTINGS v4
Table 670: RSMEMORYQT Group settings (basic)
Name
Values (Range) Unit Step Default Description
Memory Disabled
Enabled
- - Enabled Operating mode of the memory function
1MRK 502 066-UUS B Section 15
Logic
977