PID-3814-OUTPUTSIGNALS v4
Table 674: SRMEMORYQT Output signals
Name Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal
15.7.9.3 Settings
PID-3814-SETTINGS v4
Table 675: SRMEMORYQT Group settings (basic)
Name Values (Range) Unit Step Default Description
Memory Disabled
Enabled
- - Enabled Operating mode of the memory function
15.7.9.4 Technical data
GUID-341562FB-6149-495B-8A63-200DF16A5590 v1
Table 676: Number of SRMEMORYQT instances
Logic block Quantity with cycle time
3 ms 8 ms 100 ms
SRMEMORYQT - 10 30
15.7.10 Settable timer function block TIMERSETQT
GUID-582D9F19-9974-40D6-95EB-7BAD72910748 v2
GUID-3830BCA7-4876-481E-B5AC-2104675232E7 v4
The Settable timer function block (TIMERSETQT) has two outputs for delay of the input signal at
pick-up and drop-out. The timer has a settable time delay (
t
). It also has an
Operation
setting
On/Off
that controls the operation of the timer.
When the output changes value, the timestamp of the output signal is updated. The supported
“quality” state bits are propagated from the input to the output at each execution cycle. A change
of these bits will not lead to an updated timestamp on the output.
TIMERSETQT can propagate the quality, value and the timestamps of the signals via IEC61850.
15.7.10.1 Function block
GUID-13589BAE-38AE-46A1-8E9F-94BCD1CBCBF1 v1
TIMERSETQT
INPUT ON
OFF
IEC14000068-1-en.vsd
IEC14000068 V1 EN-US
Figure 511: TIMERSETQT function
15.7.10.2 Signals
GUID-4543C4C9-FAE2-4328-8DE2-4A5756A020E9 v1
1MRK 502 066-UUS B Section 15
Logic
979
Technical manual