PID-3816-INPUTSIGNALS v4
Table 677: TIMERSETQT Input signals
Name Type Default Description
INPUT BOOLEAN 0 Input signal
PID-3816-OUTPUTSIGNALS v4
Table 678: TIMERSETQT Output signals
Name Type Description
ON BOOLEAN Output signal, pick-up delayed
OFF BOOLEAN Output signal, drop-out delayed
15.7.10.3 Settings
PID-3816-SETTINGS v4
Table 679: TIMERSETQT Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Disabled/Enabled
t 0.000 -
90000.000
s 0.001 0.000 Delay for settable timer n
15.7.10.4 Technical data
GUID-B6231B97-05ED-40E8-B735-1E1A50FDB85F v1
Table 680: Number of TIMERSETQT instances
Logic block Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
TIMERSETQT - 10 30 (0.000–90000.000) s ±0.5% ±10 ms
15.7.11 Exclusive OR function block XORQT
GUID-76ADACC1-A273-4100-BE62-99BCDABFEB7A v2
GUID-62986D87-1690-499E-B8D3-1F51D2DA191E v3
The exclusive OR function (XORQT) function is used to generate combinatory expressions with
boolean variables. XORQT function has two inputs and two outputs. One of the outputs is
inverted. The output signal OUT is 1 if the input signals are different and 0 if they are equal.
Table 681: Truth table for XORQT function block
INPUT1
INPUT2 OUT NOUT
0 0 0 1
0 1 1 0
1 0 1 0
1 1 0 1
Section 15 1MRK 502 066-UUS B
Logic
980
Technical manual