Name Type Default Description
IN5 BOOLEAN 0 Input 5
IN6 BOOLEAN 0 Input 6
IN7 BOOLEAN 0 Input 7
IN8 BOOLEAN 0 Input 8
IN9 BOOLEAN 0 Input 9
IN10 BOOLEAN 0 Input 10
IN11 BOOLEAN 0 Input 11
IN12 BOOLEAN 0 Input 12
IN13 BOOLEAN 0 Input 13
IN14 BOOLEAN 0 Input 14
IN15 BOOLEAN 0 Input 15
IN16 BOOLEAN 0 Input 16
PID-3606-OUTPUTSIGNALS v3
Table 688: B16I Output signals
Name Type Description
OUT INTEGER Output value
15.10.4 Monitored data
PID-3606-MONITOREDDATA v4
Table 689: B16I Monitored data
Name Type Values (Range) Unit Description
OUT INTEGER - - Output value
15.10.5 Settings
ABBD8E283673 v3
The function does not have any parameters available in the local HMI or PCM600.
15.10.6 Operation principle
SEMOD175737-4 v5
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to 16 binary
inputs INx, where 1≤x≤16, to an integer. Each INx represents a value according to the table below
from 0 to 32768. This follows the general formula: INx = 2
x-1
where 1≤x≤16. The sum of all the values
on the activated INx will be available on the output OUT as a sum of the integer values of all the
inputs INx that are activated. OUT is an integer. When all INx (where 1≤x≤16) are activated, that is =
Boolean 1, it corresponds to that integer 65535 is available on the output OUT. The B16I function is
designed for receiving up to 16 booleans input locally. If the BLOCK input is activated, it will freeze
the output at the last value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
1MRK 502 066-UUS B Section 15
Logic
985
Technical manual