Name Type Default Description
IN8 BOOLEAN 0 Input 8
IN9 BOOLEAN 0 Input 9
IN10 BOOLEAN 0 Input 10
IN11 BOOLEAN 0 Input 11
IN12 BOOLEAN 0 Input 12
IN13 BOOLEAN 0 Input 13
IN14 BOOLEAN 0 Input 14
IN15 BOOLEAN 0 Input 15
IN16 BOOLEAN 0 Input 16
PID-6944-OUTPUTSIGNALS v2
Table 692: BTIGAPC Output signals
Name Type Description
OUT INTEGER Output value
15.11.5 Settings
ABBD8E283673 v3
The function does not have any parameters available in the local HMI or PCM600.
15.11.6 Monitored data
PID-6944-MONITOREDDATA v2
Table 693: BTIGAPC Monitored data
Name Type Values (Range) Unit Description
OUT INTEGER - - Output value
15.11.7 Operation principle
SEMOD158425-4 v6
The Boolean 16 to integer conversion with logic node representation function (BTIGAPC) will
transfer a combination of up to 16 binary inputs INx, where 1≤x≤16, to an integer. Each INx
represents a value according to the table below from 0 to 32768. This follows the general formula:
INx = 2
x-1
where 1≤x≤16. The sum of all the values on the activated INx will be available on the
output OUT as a sum of the integer values of all the inputs INx that are activated. OUT is an
integer. When all INx (where 1≤x≤16) are activated, that is = Boolean 1, it corresponds to that
integer 65535 is available on the output OUT. If the BLOCK input is activated, it will freeze the
logical outputs at the last value.
Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block BTIGAPC.
Section 15 1MRK 502 066-UUS B
Logic
988
Technical manual