Name Type Description
OUT11 BOOLEAN Output 11
OUT12 BOOLEAN Output 12
OUT13 BOOLEAN Output 13
OUT14 BOOLEAN Output 14
OUT15 BOOLEAN Output 15
OUT16 BOOLEAN Output 16
15.12.5 Setting parameters
ABBD8E242451 v3
The function does not have any parameters available in local HMI or Protection and Control IED
Manager (PCM600)
15.12.6 Operation principle
SEMOD158385-4 v4
With integer 15 on the input INP the OUT1 = OUT2 = OUT3= OUT4 =1 and the remaining OUTx = 0
for (5≤x≤16).
OUTx represents a value when activated. The value of each of the OUTx is in accordance with the
table IB16_1. When not activated the OUTx has the value 0.
In the above example when integer 15 is on the input INP the OUT1 has a value =1, OUT2 has a value
=2, OUT3 has a value =4 and OUT4 has a value =8. The sum of these OUTx is equal to 1 + 2 + 4 + 8 =
15.
This follows the general formulae: The sum of the values of all OUTx = 2
x-1
where 1≤x≤16 will be
equal to the integer value on the input INP.
The Integer to Boolean 16 conversion function (IB16) will transfer an integer with a value between 0
to 65535 connected to the input INP to a combination of activated outputs OUTx where 1≤x≤16.
The sum of the values of all OUTx will then be equal to the integer on input INP. The values of the
different OUTx are according to the table below. When an OUTx is not activated, its value is 0.
When all OUTx where 1≤x≤16 are activated that is = Boolean 1 it corresponds to that integer 65535
is connected to input INP. The IB16 function is designed for receiving the integer input locally. If
the BLOCK input is activated, it will freeze the logical outputs at the last value.
Values of each of the different OUTx from function block IB16 for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block IB16.
Name of OUTx Type Description Value when activated Value when
deactivated
OUT1 BOOLEAN Output 1 1 0
OUT2 BOOLEAN Output 2 2 0
OUT3 BOOLEAN Output 3 4 0
OUT4 BOOLEAN Output 4 8 0
OUT5 BOOLEAN Output 5 16 0
Table continues on next page
1MRK 502 066-UUS B Section 15
Logic
991
Technical manual