15.13.2 Functionality
SEMOD158421-5 v8
Integer to boolean conversion with logic node representation function ITBGAPC is used to
transform an integer which is transmitted over IEC 61850 and received by the function to 16 binary
coded (logic) output signals.
ITBGAPC function can only receive remote values over IEC 61850 when the R/L (Remote/Local)
push button on the front HMI, indicates that the control mode for the operator is in position R
(Remote i.e. the LED adjacent to R is lit ), and the corresponding signal is connected to the input
PSTO ITBGAPC function block. The input BLOCK will freeze the output at the last received value
and blocks new integer values to be received and converted to binary coded outputs.
15.13.3 Function block
SEMOD158435-4 v4
ITBGAPC
BLOCK
PSTO
OUT1
OUT2
OUT3
OUT4
OUT5
OUT6
OUT7
OUT8
OUT9
OUT10
OUT11
OUT12
OUT13
OUT14
OUT15
OUT16
IEC14000012-1-en.vsd
IEC14000012 V1 EN-US
Figure 517: ITBGAPC function block
15.13.4 Signals
PID-3627-INPUTSIGNALS v6
Table 698: ITBGAPC Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Block of function
PSTO INTEGER 1 Operator place selection
PID-3627-OUTPUTSIGNALS v6
Table 699: ITBGAPC Output signals
Name Type Description
OUT1 BOOLEAN Output 1
OUT2 BOOLEAN Output 2
OUT3 BOOLEAN Output 3
OUT4 BOOLEAN Output 4
OUT5 BOOLEAN Output 5
Table continues on next page
1MRK 502 066-UUS B Section 15
Logic
993
Technical manual