EasyManua.ls Logo

ABB Relion 670 series - Section 4 Analog and Binary Signal Transfer for Line Differential Protection; Communication Channels for Line Differential Protection

ABB Relion 670 series
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 4 Analog and binary signal transfer for line
differential protection
4.1 Communication channels for line differential
protection
M12022-69 v7
The line differential protection function uses 64 kbit/s or 2 Mbit/s communication
channels to exchange telegrams between the line differential protection IEDs.
These telegrams contain current sample values, time information, trip signals,
block signals, alarm signals and 8/192 binary signals, which can be used for any
purpose. Each IED can have a maximum of four communication channels.
On a two terminal line there is a need for one communication channel provided that
there is only one CT at each line end (see Figure
13).
IED
Protected zone
IEC05000437-2-en.vsdx
IED
IEC05000437 V2 EN-US
Figure 13: Two-terminal line
In case of 1½ breaker arrangements or ring buses, a line end has two CTs (see
Figure 14).
IE D
Protected zone
IED
IEC05000438-2-en.vsdx
IEC05000438 V2 EN-US
Figure 14: Two-terminal line with 1½ breaker
1MRK 505 382-UEN B Section 4
Analog and binary signal transfer for line differential protection
Communication set-up 670/650 series 2.2 27
Application Guide

Table of Contents

Other manuals for ABB Relion 670 series

Related product manuals