IEC10000247-1-en.vsdx
IEC10000247 V1 EN-US
Figure 50: Tab selection in SMT for binary input and output configuration
Figure 51 shows a configuration of LDCM Hardware Channel and SMBI in the
Binary Inputs tab in SMT Connection between hardware (LDCM) and software
(SMBI) is indicated by an X.
IEC10000245-1-en.vsdx
IEC10000245 V1 EN-US
Figure 51: Connection (indicated by X) established between LDCM and SMBI
To rename a chosen Hardware Channel in SMT:
1. Select the channel you want to rename.
2. Open Object Properties.
3. Rename the channel in the User Defined Name field and save.
1MRK 505 382-UEN B Section 4
Analog and binary signal transfer for line differential protection
Communication set-up 670/650 series 2.2 57
Application Guide