OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with)
30
2 (default)
1)
16-bit
analog
input
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
2)
30 3 32-bit
analog
input
without flag
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
2)
30 4 16-bit
analog
input
without flag
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response) 00, 01 (start-stop)
17, 28 (index)
2)
32 0 Analog
change
event –
any
variation
1 (read) 06 (no range, or all)
07, 08 (limited qty)
32 1 32-bit
analog
change
event
without
time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
32 2 16-bit
analog
change
event
without
time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
32 3 32-bit
analog
change
event with
time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
32
4 (default)
1)
16-bit
analog
change
event with
time
1 (read) 06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
50 0 Time and
date
50
1 (default)
1)
Time and
date
1 (read) 00, 01 (start-stop)
06 (no range, or all)
07 (limited qty = 1l)
08 (limited qty)
129 (response) 00, 01 (start-stop)
17, 28 (index)
2)
2 (write) 07 (limited qty = 1l)
50 3 Time and
date last
recorded
time
2 (write) 07 (limited qty)
51 1 Time and
date CTO
129 (response)
130 (unsol. resp)
07 (limited qty)
(qty = 1)
51 2 Unsynchro
nized time
and date
CTO
129 (response)
130 (unsol. resp)
07 (limited qty)
(qty = 1)
Table continues on next page
1MRS757807 B Section 3
DNP3 protocol implementation
Remote Monitoring and Control REC615 67
Point List Manual