4.2.2.11 Settings
Table 352: DEFLPDEF Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 0.010...5.000 xIn 0.005 0.010 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scal-
ing the start value
Directional mode
1=Non-directional
2=Forward
3=Reverse
2=Forward Directional mode
Time multiplier 0.05...15.00 0.01 1.00 Time multiplier
in IEC/ANSI IDMT
curves
Operating curve
type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
15=IEC Def. Time Selection of time
delay curve type
Operate delay time 50...200000 ms 10 50 Operate delay time
Characteristic an-
gle
-179...180 deg 1 -90 Characteristic an-
gle
Max forward angle 0...180 deg 1 80 Maximum phase
angle in forward di-
rection
Max reverse angle 0...180 deg 1 80 Maximum phase
angle in reverse di-
rection
Min forward angle 0...180 deg 1 80 Minimum phase an-
gle in forward di-
rection
Min reverse angle 0...180 deg 1 80 Minimum phase an-
gle in reverse direc-
tion
Voltage start value 0.010...1.000 xUn 0.001 0.010 Voltage start value
Table 353: DEFLPDEF Group settings (Advanced)
Parameter
Values (Range) Unit Step Default Description
Type of reset curve
1=Immediate
2=Def time reset
1=Immediate Selection of reset
curve type
Table continues on the next page
1MRS758755 C Protection functions
REC615 & RER615
Technical Manual
321