Figure 188: Definition of the relay characteristic angle
The phase angle difference is calculated based on the
Characteristic angle
setting
(also known as Relay Characteristic Angle (RCA) or Relay Base Angle or Maximum
Torque Angle (MTA)). The
Characteristic angle
setting is done based on the method
of earthing employed in the network. For example, in case of an unearthed network,
the
Characteristic angle
setting is set to -90°, and in case of a compensated
network, the
Characteristic angle
setting is set to 0°. In general,
Characteristic
angle
is selected so that it is close to the expected fault angle value, which results
in maximum sensitivity.
Characteristic angle
can be set anywhere between -179°
to +180°. Thus, the effective phase angle (ϕ) for calculating the residual power
considering characteristic angle is according to the equation.
φ
=
( )
( )Uo Io Characteristic angle
(Equation 29)
In addition, the characteristic angle can be changed via the control signal RCA_CTL.
The RCA_CTL input is used in the compensated networks where the compensation
coil sometimes is temporarily disconnected. When the coil is disconnected, the
compensated network becomes isolated and the
Characteristic angle
setting must
be changed. This can be done automatically with the RCA_CTL input, which results
in the addition of -90° in the
Characteristic angle
setting.
The value (ANGLE_RCA) is available in the monitored data view.